For Enclosure Solutions Wall Systems Using HIGH MASS NON-COMBUSTIBLE EXTERIOR CLADDING | ||
Wall Component | Materials | |
Base Wall System | • Concrete (cast-in-place or pre-cast)
• Concrete Masonry Units • Steel Stud Framing, minimum 3 5/8″ depth, minimum 20 gauge, maximum 16 inches on center spacing, with lateral bracing every 4 ft vertically. Cover on the interior with 1 layer of 5/8″ thick, Type X, gypsum wallboard. |
|
Floorline Firestopping
If a fire resistance rated floor or floor/ceiling assembly IS required use option 1: If a fire resistance rated floor assembly IS NOT required use option 2: |
1. Install an ASTM E2307 tested or evaluated perimeter fire containment joint assembly.
Thermafiber® Safing Insulation Thermafiber® Impasse Insulation Hanger System 2. Install a mineral wool fire stop, 4 pcf density, attached with Z-clips or equivalent continuously at each floor line and/or in each stud cavity if the stud framing is continuous past the floor line. |
|
Stud Cavity Insulation | • EcoTouch® Flame Spread 25 Batt Insulation (faced fiber glass)
• EcoTouch® Batt Insulation (unfaced fiber glass) • Thermafiber® Ultrabatt™ (faced or unfaced mineral wool) • Any non-combustible insulation (faced or unfaced) • Spray Polyurethane Foam, Demilec Sealaction 500 (0.5 pcf maximum, used only with gypsum exterior sheathing) • None |
|
Exterior Sheathing | • None
• Gypsum Sheathing, 1/2″, exterior grade • Gypsum Sheathing, 5/8″, Type X, exterior grade |
|
Air & Water Barrier
All air & water barriers are to be installed at recommended application rates and in strict accordance with the manufacturer’s installation instructions. Verify vapor resistance properties if required. |
• None
• Air/water barrier membrane selected from Appendix B and installed on the base wall behind the continuous insulation (CI) • Owens Corning® JointSealR® Foam Joint Tape applied to the joints of FOAMULAR® XPS continuous insulation • DuPont Tyvek® CommercialWrap applied over continuous insulation • Pactiv GreenGuard® Max Building Wrap applied over continuous insulation |
|
Continuous Insulation | • FOAMULAR® 250 XPS
• FOAMULAR® High R CW Plus • FOAMULAR® CW15 XPS • FOAMULAR® CW25 XPS • Thermafiber® Rainbarrier® HD • Thermafiber® Rainbarrier® 45 |
ASTM C578 Type IV ASTM C578 Type IV ASTM C578 Type X ASTM C578 Type IV
Unfaced, minimum 2″ thick, mechanically attached per manufacturer’s recommendations, continuous over air & weather barrier system if selected unfaced, minimum 2″ thick, mechanically attached per manufacturer’s recommendations, continuous over air & weather barrier system if selected. |
Exterior Cladding/Veneer | • Brick Veneer: Nominal 4″ thick, clay brick. Veneer anchors, standard types, installed maximum 24″ o.c. vertically on each stud, or, continuous ladder tie type if CMU backup is utilized. Maximum 2″ air space between continuous insulation and brick.
• Concrete Masonry Units: Minimum 4″ thick. Maximum 2″ air space between continuous insulation and CMU. • Concrete Panels: Minimum 2″ thick. Maximum 2″ air space between continuous insulation and concrete. |
*Options: FOAMULAR® may be installed directly over steel stud framing, with joints sealed with JointSealR®
Exterior Cladding/Veneer | • EIFS: Polymer Modified (PM) Exterior Insulation Finish Systems, with XPS base. Details as NFPA 285 tested and specified by PM EIFS manufactured.
• Insulated Concrete Sandwich Panels: Minimum 2″ thick outer face wythe. Maximum 2″ air space between continuous insulation and concrete. • Stone Veneer: Minimum 2″ thick, limestone or natural stone veneer, or minimum 1 1/2″ thick manufactured stone veneer. May use any standard closed joint installation such as ship-lap, etc. • Stucco: Minimum 7/8″ thick, exterior cement plaster and lath. Lath mechanically attached. |
Window & Door Openings and Transition Details | • FOAMULAR® 250 XPS Continuous Insulation
• Thermafiber® Rainbarrier® Continuous Insulation • Steel Stud (head, jamb, sill) • CMU (head, jamb, sill) • Transition Between Cladding Types • Flash window, door, and other exterior penetrations with limited amounts of acrylic, asphalt, or butyl-based flashing tape, max. 12″ width. |
For Enclosure Solutions Wall Systems Using COMBUSTIBLE or LOW-MASS NON-COMBUSTIBLE EXTERIOR CLADDING | |
Wall Component | Materials |
Base Wall System | • Concrete (cast-in-place or pre-cast)
• Concrete Masonry Units • Steel Stud Framing, minimum 3 5/8″ depth, minimum 20 gauge, maximum 16 inches on center spacing, with lateral bracing every 4 ft vertically. Cover on the interior with 1 layer of 5/8″ thick, Type X, gypsum wallboard. |
Floorline Firestopping
If a fire resistance rated floor or floor/ceiling assembly IS required use option 1: If a fire resistance rated floor assembly IS NOT required use option 2: |
1. Install an ASTM E2307 tested or evaluated perimeter fire containment joint assembly.
Thermafiber® Safing Insulation Thermafiber® Impasse Insulation Hanger System 2. Install a mineral wool fire stop, 4 pcf density, attached with Z-clips or equivalent continuously at each floor line and/or in each stud cavity if the stud framing is continuous past the floor line. |
Stud Cavity Insulation | • EcoTouch® Flame Spread 25 Batt Insulation (faced fiber glass)
• EcoTouch® Batt Insulation (unfaced fiber glass) • Thermafiber® Ultrabatt™ (faced or unfaced mineral wool) • Any non-combustible insulation (faced or unfaced) • Spray Polyurethane Foam, Demilec Sealaction 500 (0.5 pcf maximum, used only with gypsum exterior sheathing) • None |
Exterior Sheathing
Options* |
• None
• Gypsum Sheathing, 1/2″, exterior grade • Gypsum Sheathing, 5/8″, Type X, exterior grade |
Air & Water Barrier
All air & water barriers are to be installed at recommended application rates and in strict accordance with the manufacturer’s installation instructions. Verify vapor resistance properties if required. |
• None
• W. R. MEADOWS AIR-SHIELD® LSR • W. R. MEADOWS AIR-SHIELD® LMP (Gray) • W. R. MEADOWS AIR-SHIELD® LMP (Black) • W. R. MEADOWS AIR-SHIELD® TMP |
Continuous Insulation (CI) | • Thermafiber® Rainbarrier® 45, unfaced, minimum 2″ thick, mechanically attached per manufacturer’s recommendations, continuous over air & weather barrier system if selected.
• Thermafiber® Rainbarrier® HD, unfaced, minimum 2″ thick, mechanically attached per manufacturer’s recommendations, continuous over air & weather barrier system if selected. |
Exterior Cladding/Veneer | • Any Combustible Veneer that has been tested and documented to be NFPA 285 compliant
• Brick Veneer: Nominal 4″ thick, clay brick. Veneer anchors, standard types, installed maximum 24″ o.c. vertically on each stud, or, continuous ladder tie type if CMU backup is utilized. Maximum 2″ air space between continuous insulation and brick. • Concrete Masonry Units: Minimum 4″ thick. Maximum 2″ air space between continuous insulation and CMU. • Concrete Panels: Minimum 2″ thick. Maximum 2″ air space between continuous insulation and concrete. • Fiber Cement or Cement Board Siding: Fastened to the structural backup wall or to Z-furring, girts, or other secondary framing as recommended by the cladding manufacturer. • Metal Panel: Single skin steel, aluminum, copper, etc, fastened to the structural backup wall or to Z-furring, girts, or other secondary framing as recommended by the cladding manufacturer. • Metal Composite Material (MCM): Use any MCM that has been tested and documented to be NFPA 285 compliant. Fastened to the structural backup wall or to Z-furring, girts, or other secondary framing or clip system as recommended by the cladding manufacturer. • Stone Veneer: Minimum 2″ thick, limestone or natural stone veneer, or minimum 1 1/2″ thick manufactured stone veneer. May use any standard open or closed joint installation such as ship-lap, etc. • Terra Cotta Panels: Terra Cotta cladding system, minimum 1 1/4″ thick, with open or closed joint installation such as ship-lap, etc. |
Window & Door Openings and Transition Details | • Thermafiber® Rainbarrier® Continuous Insulation
• Steel Stud (head, jamb, sill) • CMU (head, jamb, sill) • Transition Between Cladding Types • Flash window, door, and other exterior penetrations with limited amounts of acrylic, asphalt, or butyl-based flashing tape, max. 12″ width. |
Information obtained from Owens Corning® Enclosure Solutions
08-2020
Full NFPA testing documents are available. Please contact us to request these documents.